ER PLUS

DESCRIPTION
90° electric actuator, PA6 housing UL 94 V-0 with secured manual override for torques of 10-20-35-60-100Nm and in accordance with CE-ROHS-REACH Directives.

VERSIONS
  • Standard version: 90° - MULTIVOLT: operating time from 6s to 20s (without load)
  • Long operating version: 90° - MULTIVOLT: operating time from 34s to 110s (without load)
  • Different possible rotation angles
  • Also available: FAILSAFE, POSI, 3-position and Bluetooth® versions.

TECHNICAL DATA
  • Duty rating S4 50% (IEC34)
  • Temperature: -10°C to +55°C
  • Enclosure: IP66
  • Weight: 1Kg - 2.1Kg
STANDARD EQUIPMENT
  • Multivoltage actuator:
  • 100V to 240V 50/60Hz (100V to 350V DC)
    15V to 30V 50/60Hz (12V to 48V DC)
  • On-off or 3 modulating points control
  • 4 adjustable limit switches 5A
  • Removable adaptation plates:
  • ER 10-35Nm: F03-F04-F05
    ER 35-100Nm: F05-F07
  • Star drive nut
  • Secured manual override
  • Modular position indicator
  • Integrated anticondensation heater
  • Torque limiter monitored by software
  • Motor failure feedback relay (normal duty, failure)
  • RS485 connection
  • Mechanical travel stops at 90°
  • 1 3P+T DIN43650 connector + 1 ISO M20 (ISO - NPT adapters available as option)


     

       
User manual
ER PLUS user manual


Technical datasheet
ER PLUS technical datasheet


Standards
ER PLUS standards


Catalogue
Valpes actuators catalogue


2D & 3D files
Download actuators 2D and 3D files
Drive Depth (mm) ISO connection Diameter (mm) threading Depth (mm) Screws number
Star 14 16 F03 36 M5 14,2 4
Star 22 24 F04 42 M5 14,2 4
F05 (ER10/20/35) 50 M6 14,2 4
F05 (ER35/60/100) 50 M6 16,4 4
F07 70 M8 16,4 4


Standard range    
Code Star drive nut
Connection
Torque Voltage supplies Power Operating time (90°)    
without load with load  
ER10.X0A.G00 1) 14/F03-F04-F05 10Nm 100V to 240V 50/60Hz (100V to 350V DC) 15W 9s 11s  
ER10.X0B.G00 1) 14/F03-F04-F05 10Nm 15V to 30V 50/60Hz (12V to 48V DC) 15W 9s 11s  
ER20.X0A.G00 1) 14/F03-F04-F05 20Nm 100V to 240V 50/60Hz (100V to 350V DC) 15W 9s 12s  
ER20.X0B.G00 1) 14/F03-F04-F05 20Nm 15V to 30V 50/60Hz (12V to 48V DC) 15W 9s 12s  
ER35.X0A.G00 1) 14/F03-F04-F05 35Nm 100V to 240V 50/60Hz (100V to 350V DC) 15W 19s 26s  
ER35.X0B.G00 1) 14/F03-F04-F05 35Nm 15V to 30V 50/60Hz (12V to 48V DC) 15W 19s 24s  
ER35.90A.G00 22/F05-F07 35Nm 100V to 240V 50/60Hz (100V to 350V DC) 45W 6s 7s  
ER35.90B.G00 22/F05-F07 35Nm 15V to 30V 50/60Hz (12V to 48V DC) 45W 6s 7s  
ER60.90A.G00 22/F05-F07 60Nm 100V to 240V 50/60Hz (100V to 350V DC) 45W 10s 12s  
ER60.90B.G00 22/F05-F07 60Nm 15V to 30V 50/60Hz (12V to 48V DC) 45W 10s 12s  
ER100.90A.G00 22/F05-F07 100Nm 100V to 240V 50/60Hz (100V to 350V DC) 45W 20s 23s  
ER100.90B.G00 22/F05-F07 100Nm 15V to 30V 50/60Hz (12V to 48V DC) 45W 19s 22s  
long operating time range    
ER35.93A.G00 22/F05-F07 35Nm 100V to 240V 50/60Hz (100V to 350V DC) 45W 34s 40s  
ER35.93B.G00 22/F05-F07 35Nm 15V to 30V 50/60Hz (12V to 48V DC) 45W 34s 41s  
ER60.93A.G00 22/F05-F07 60Nm 100V to 240V 50/60Hz (100V to 350V DC) 45W 67s 79s  
ER60.93B.G00 22/F05-F07 60Nm 15V to 30V 50/60Hz (12V to 48V DC) 45W 68s 79s  
ER100.93A.G00 22/F05-F07 100Nm 100V to 240V 50/60Hz (100V to 350V DC) 45W 110s 119s  
ER100.93B.G00 22/F05-F07 100Nm 15V to 30V 50/60Hz (12V to 48V DC) 45W 110s 119s  
1) Conversion sleeves star 14 to square 9-11 and removable plate F03/F05 or F04 (can be ordered mounted)    
Options    
EPR...B 1) 100 / 1000 / 5000 / 10000 Ohms feedback potentiometer  
EPT.C 2) 0-20mA / 4-20mA / 0-10V transmitter  
EFC.2 Card with 2 Extra limit switches  
VIB Version for applications with vibrations  
1) Specify the model
2) Only for a travel time higher or equal to 10s
   
Electric connections    
ECD.1A 1x 3P+T DIN 43650 connector  
ECM.1 1x 3P+T M12 connector  
ECM.2 2x 3P+T M12 connectors  
NPT.1 3) 1x ISO M20 to 1/2" NPT adapter (ER PLUS • compulsory for CSA)  
NPT.2 3) 2x ISO M20 to 1/2" NPT adapters (VR / VS • compulsory for CSA)  
ECD.NPT 3) 1x DIN43650 power supply connector with 1/2" NPT sized entry  
ECD.1A.NPT 3) 1x DIN43650 feedback connector with 1/2" NPT sized entry  
3) NPT connection compulsory for CSA standard    




Site map

Products
Valpes electric actuators
Options
Electric connection

Valpes
The company
News
Sales team
Contact us
Location

Download
Technical datasheets
User manuals
Standards
Files 2D/3D
Catalogue and pricelist
High resolution photos

Support
Frequently asked questions
Video tutorials

Valpes
Z.I. Centr'alp • 89 rue des étangs
38430 Moirans • France
Tél. +33 (0) 4 76 35 06 06 • Fax +33 (0) 4 76 35 14 34
valpes-info@wattswater.com • valpes-adv@wattswater.com (for orders)

Private acces request        |        careers        |        General sales conditions        |        Website using conditions        |        Privacy policy