VT
Description
Electric actuator, aluminium housing and polyamide PA6 UL 94 V-0 or aluminium cover (option) with manual override by hand wheel, for torques from 600 to 2400 Nm and in accordance with CE-ROHS-REACH Directives.
Versions
- 90° standard version and 180° or 270° version (on request)
- Version for marine applications. High durability coating, 15-year warranty
- Also available in ATEX version (600-1000Nm)
Technical Data
- 3-phase 50 Hz 400 V
- 3 modulating points control
- 4 adjustable limit switches 5 A
- Connection according to ISO5211 standard:
- VT600-1000 Nm: F10/F12
- VT1500-2400 Nm: F12/F14/F16
- Star drive
- VT600-1000Nm: 36 mm
- VT1500-2400Nm: 46 mm
- Manual override
- Regulated anticondensation heater
- Mechanical torque limiter
- Failure feedback relay (normal duty, failure)
- Visual position indicator
- Adjustable mechanical limit stops
- Duty rating: S4 5 0% (IEC34)
- Working temperature: -20 °C to +70 °C
- Enclosure IP68:
- 2 m / 72 h (plastic cover)
- 5 m / 72 h (aluminium cover)
- Weight:
- VT600-1000Nm: 24 kg
- VT1500-2400Nm: 53 kg
- 2x ISO M20 cable glands
VT600-1000Nm
VT1500-2400Nm
| VT 600-1000 Nm | ||||||||||
| Drive | Depth (mm) | ISO connection | Diameter (mm) | threading | Depth (mm) | Screws number | Screws maximal length (mm + valve connection plate height) |
|||
| 36 | 41 | F10 | 102 | M10 | 25 | 4 | 20 | |||
| F12 | 125 | M12 | 30 | 4 | 25 | |||||
| VT 1500-2400 Nm | ||||||||||
| Drive | Depth (mm) | ISO connection | Diameter (mm) | threading | Depth (mm) | Screws number | Screws maximal length (mm + valve connection plate height) |
|||
| 46 | 50 | F12 | 125 | M12 | 20 | 4 | 15 | |||
| F14 | 140 | M16 | 25 | 4 | 20 | |||||
| F16 | 165 | M20 | 30 | 4 | 25 | |||||
| Code | Star drive nut Connection |
Torque | Voltage supplies | Power | Operating time (90°) | |||
| VT600.A09.R00 | 36 F10/F12 | 600Nm | 3-phase 50Hz 400V | 250W | 38s | |||
| VT1000.A09.R00 | 36 F10/F12 | 1000Nm | 3-phase 50Hz 400V | 250W | 38s | |||
| VT1500.B09.R00 | 46 F14 | 1500Nm | 3-phase 50Hz 400V | 250W | 113s | |||
| VT1500.C09.R00 | 46 F12/F16 | 1500Nm | 3-phase 50Hz 400V | 250W | 113s | |||
| VT2400.B09.R00 | 46 F14 | 2400Nm | 3-phase 50Hz 400V | 250W | 113s | |||
| VT2400.C09.R00 | 46 F12/F16 | 2400Nm | 3-phase 50Hz 400V | 250W | 113s | |||
| Options | ||||||||
| EPR…B 1) | 100 / 1000 / 5000 / 10000 Ohms feedback potentiometer | |||||||
| EPT.C 2) | 0-20mA / 4-20mA / 0-10V transmitter | |||||||
| EFC.2 | Card with 2 Extra limit switches | |||||||
| ECA | Aluminium cover (+0,9kg) | |||||||
| MARINE | High durability marine coating (require ECA option) | |||||||
| 1) Specify the model 2) Only for a travel time higher or equal to 10s |
||||||||
| Electric connections | ||||||||
| ECM.1 | 1x 3P+T M12 connector | |||||||
| ECM.2 | 2x 3P+T M12 connectors | |||||||